Surge arrester ETITEC M T12 950/12,5 4Y 002440810
Specifications
- ETI Code:
- 002440810
- Description:
- ETITEC M T12 950/12,5 4Y
- Class name:
- Surge arrester
- sort_order:
- 1
- id_level1:
- 2579
- l1_sort_order:
- 5505
- l2_sort_order:
- 5947
- l3_sort_order:
- 7038
- l4_sort_order:
- 7039
- l5_sort_order:
- 7040
- l6_sort_order:
- 7041
- Usage (IEC/VDE):
- I, II / B, C
- Current type:
- AC
- Function:
- SPD
- Type:
- T1, T2
- Number of poles:
- 4
- Size:
- 4 modules
- IP rating:
- IP20
- Mounting:
- DIN rail (top hat rail) 35 mm
- Catalogue Group:
- ETITEC M AC
- Number of modules:
- 4
- Up - Voltage protection level (kV):
- 4
- Leakage current:
- YES
- Applied technology:
- MOV
- Built-in depth (mm):
- 86
- Iimp(10/350) impulse current (kA):
- 12,5
- Max. discharge current Imax, 8/20 (kA):
- 50
- Remote signalisation:
- NO
- In 8/20 (kA):
- 20
- Installation:
- PV inverters protection on the AC side
Documents
Logistic Data
Product
- Net weight of the product
- 0.775 kg
- Customs tariff
- 85363090
Basic packaging
- Basic packaging quantity
- 1
- EAN code for a basic packaging
- 3838895985051
- Basic packaging weight
- 0.853 kg
Transport packaging
- Transport packaging quantity
- 4
- EAN code for a transport packaging
- 3838895985068
- Transport packaging weight
- 3.751 kg
- Pallet quantity
- 636
ETIM Clasification
- Classification
- EC001457
- Class name
- Combined arrester for power supply systems
- Degree of protection (IP), front side
- 20
- Leakage current type
- AC
- Nominal discharge surge current (8/20)
- 20
- Number of knife blade fuse holders
- 4
- System configuration DC
- Yes
- System configuration IT
- No
- System configuration TN
- No
- System configuration TN-C
- No
- System configuration TN-C-S
- No
- System configuration TN-S
- No
- System configuration TT
- No
- System configuration other
- No
- Number of poles
- 2
- Lightning impulse current (10/350 µs)
- 12,5
- Max. continuous voltage AC
- 950
- Voltage protection level
- 4
- Specific energy (W/R)
- 39
- Max. conductor cross section solid (solid, stranded)
- 35
- Max. conductor cross section flexible (fine-strand)
- 25
- Mounting method
- DIN rail (top hat rail) 35 mm
- Remote signalling
- No
- Signalling at the device
- Optical
- Test class
- Type 1 + 2
- Exhausting
- No
- Integrated backup fuse
- No
- Degree of protection (IP)
- IP20