Type some words to find content.
eg: fuse, arrestor, 00110115 technical, MCCB...
Recent searches
Tehnical support
This email address is being protected from spambots. You need JavaScript enabled to view it.

Surge arrester ETITEC EM T12 PV 1500/5 Y RC 002440583

Specifications

ETI Code:
002440583
Description:
ETITEC EM T12 PV 1500/5 Y RC
Class name:
Surge arrester
Usage (IEC/VDE):
I, II / B, C
Current type:
DC
Function:
SPD
Type:
T1, T2
Number of poles:
2
Size:
3 modules
IP rating:
IP20
Mounting:
DIN rail (top hat rail) 35 mm
Catalogue Group:
ETITEC EM PV
Number of modules:
3
Up - Voltage protection level (kV):
5
Leakage current:
YES
Applied technology:
MOV
Built-in depth (mm):
86
Iimp(10/350) impulse current (kA):
5
Max. discharge current Imax, 8/20 (kA):
30
Remote signalisation:
YES
In 8/20 (kA):
20
Iimp - Total impulse current (10/350) (kA):
5
Installation:
PV protection

Documents

Product

Net weight of the product
0.05  kg
Customs tariff
85363090  
logis_net_width
54  mm
logis_net_height
110  mm

Basic packaging

Basic packaging quantity
1  
EAN code for a basic packaging
3838895853015  
Basic packaging weight
0.055  kg

Transport packaging

Transport packaging quantity
5  
EAN code for a transport packaging
3838895853022  
Transport packaging weight
0.301  kg
Pallet quantity
900  
Classification
EC001457
Class name
Combined arrester for power supply systems
Leakage current type
DC
Number of knife blade fuse holders
MOV
Degree of protection (IP), front side
20
Nominal discharge surge current (8/20)
20
System configuration DC
Yes
System configuration IT
No
System configuration TN
No
System configuration TN-C
No
System configuration TN-C-S
No
System configuration TN-S
No
System configuration TT
No
System configuration other
No
Number of poles
2
Lightning impulse current (10/350 µs)
5
Max. continuous voltage DC
1500
Voltage protection level
5
Specific energy (W/R)
6,25
Max. conductor cross section solid (solid, stranded)
35
Max. conductor cross section flexible (fine-strand)
25
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
Other
Remote signalling
Yes
Signalling at the device
Optical
Test class
Type 1 + 2
Exhausting
No
Integrated backup fuse
No
Degree of protection (IP)
IP20
ETIM Classification – Version 7.0

Images & Diagrams

Software & drivers

Software is provided as is without any guarantees or warranty. The author is under no obligation to provide support, service, corrections, or upgrades to the free software programs or drivers.

Accessories 32

>
>
0
Your basket is empty.